100% Stator Ground Fault Protection
The 889 provides 100% Stator Ground Fault Protection for High
Resistance Grounded System (HRG), Low Resistance Grounded
(LRG) or Hybrid Grounded Systems. For HRG systems the 889
employes a unique combination of Auxiliary Overvoltage and 3rd
Harmonic Neutral Undervoltage protection elements to provide
secure, reliable protection of the stator winding. With this function
the 3rd harmonic neutral voltage variations do not need to be
considered, simplifying the settings and configuration process.
For LRG systems with parallel machines, the 889 provides ground
fault coordination ensuring only the faulted generator is islanded.
In Hybrid Grounded Systems, the 889 provides fast, dynamic
switching from low-z to high-z when an internal generator fault
is detected, reducing potential damage to the generator and
eliminating the need for additional protection devices.