Overcurrent Elements
The 889 can be used to provide backup protection for transformer
and adjacent power system equipment. Instantaneous overcurrent
(IOC) elements can be used for fast clearing of severe internal and
external (through) faults. Up to six time overcurrent protection
(TOC) elements per winding allow to coordinate with the adjacent
protection zones and act as backup protection.
• IOC protection functions are provided for phase, neutral &
ground currents
• TOC protection functions are provided for phase, neutral and
ground currents. A variety of standard time curves including
IEEE, IEC, GE Vernova IAC, I2t, definite time are provided
• FlexCurves to coordinate with adjacent protections (including
fuses) as well as transformer damage curves and thermal/
damage curves for downstream equipment Directional
protection functions are provided for phase, neutral and ground
currents. The voltage memory function enables a more reliable
relay operation, especially for faults close to the VTs.