Assembly
The input module has 16 safety-related digital inputs 48/120 VAC for contact makers. For
safely detecting a high level on the digital input, the voltage and current thresholds must be
exceeded, see Table 8.
The 8 short-circuit-proof supplies feed 2 supply outputs each (S1 to S8). One supply output
is assigned to each digital input.
The safety-related 1oo2 processor system for the I/O module controls and monitors the I/O
level. The data and states of the I/O module are made available to the processor modules
via the redundant system bus. The system bus has a redundant structure for reasons of
availability. Redundancy is only ensured if both system bus modules are inserted in the
base plates and configured in SILworX.