Safety Function
The module does not perform any safety-related functions.
The parameters and status for this module must not be used for safety functions.
Reaction in the Event of a Fault
If a module fault occurs, all outputs are switched off.
If the system bus fails, the outputs are de-energized.
The module activates the Error LED on the front plate.
Scope of Delivery
The module must be installed on a suitable connector board to be able to operate. If a Field
Termination Assembly (FTA) is use, a system cable is required to connect the connector board
to the FTA. Connector boards, system cables and FTAs are not included within the scope of
delivery.
The connector boards are described in Chapter 3.6. the system cables are described in
Chapter 3.7. The FTAs are described in own manuals.
Structure
The module is equipped with 12 relay outputs; each of these outputs can be energized by a
relay.
All 12 relay outputs are electrically safely isolated from one another. Each relay output is safely
isolated from the voltage supply of the module by its own contact circuit. For safe insulation, the
air and creeping distances are designed in accordance with IEC 61131-2 for overvoltage class II
up to 300 V.