Product Description
The DI 32 01 is a module with 32 digital inputs and is used for the modular F60 system. The
inputs are galvanically separated to the I/O bus.
The module can be inserted in the F60 subrack’s slot 3…8. Slots 1 and 2 are reserved for the
power supply module and central module, respectively.
The module has been certified by the TÜV for safety-related applications up to SIL 3
(IEC 61508. IEC 61511 and IEC 62061), Cat. 4 and PL e (EN ISO 13849-1) and SIL 4
(EN 50126. EN 50128 and EN 129).
Further safety standards, application standards and test standards are specified in the
certificates available on the HIMA website.
A fault reaction is triggered if one of the following faults occurs:
Cross-circuit between two parallel wires.
Improper connections of two lines (e.g., TO 2 to DI 3).
Earth fault of a line (with earthed ground only).
Open-circuit or open contacts, i.e., including when one of the two EMERGENCY STOP
switches mentioned above has been engaged.
The fault reaction includes the following actions:
The ERROR LED on the controller’s front plate blinks.
The inputs are set to 0.
An evaluable error code is created.