Hardware Features
• The 32-channel HART module can have a HIMax baseplate inserted
in any of the slots, with the exception of the slot reserved for the system
bus module.
• The module can be combined with analog input or output modules in
a mono or redundant design by using connector boards.
• HART communication for up to 3200 I/Os per HIMax system (calculated
based on HIMax performance:
100 I/O modules + 100 X-HART modules x 32 field instruments)
HIMax HART Package
• Import data for predefined HART variables + CUT LDB
• Predefined library of modules for all standard HART commands – 15
implemented commands
• Simple base for building your own command modules on the application
level, including possibility for command sequences
HIMax HART Data Tunneling
• HART data is transmitted from the X-HART modules via the internal system
bus to the assigned X-COM module.
• From the X-COM module, HART data is transferred via HART over IP Protocol
version 7 (IPv7) to the asset management system or the HART OPC server.