Hardware Features

• The 32-channel HART module can have a HIMax baseplate inserted

in any of the slots, with the exception of the slot reserved for the system

bus module.

• The module can be combined with analog input or output modules in

a mono or redundant design by using connector boards.

• HART communication for up to 3200 I/Os per HIMax system (calculated

based on HIMax performance:

100 I/O modules + 100 X-HART modules x 32 field instruments)

HIMax HART Package

• Import data for predefined HART variables + CUT LDB

• Predefined library of modules for all standard HART commands – 15

implemented commands

• Simple base for building your own command modules on the application

level, including possibility for command sequences

HIMax HART Data Tunneling

• HART data is transmitted from the X-HART modules via the internal system

bus to the assigned X-COM module.

• From the X-COM module, HART data is transferred via HART over IP Protocol

version 7 (IPv7) to the asset management system or the HART OPC server.