Product Description

The X‑COM 01 E communication module is intended for use in the programmable electronic

system (PES) HIMax.

The module can be inserted into any of the base plate slots with the exception of the slots

reserved for system bus modules. Refer to the system manual (HI 801 001 E) for details.

The module is approved for use in the safety-related HIMax system and can be employed to

transport safety-related protocols.

The module ensures communication with systems via Ethernet and fieldbus interfaces with

SafeEthernet and diverse standard protocols.

Safety Function

No safety function is performed by the communication module.

Response in the Event of a Fault

If faults occur, the module enters the temporary STOP_ERROR state. The module is then

rebooted and restarted from the INIT state.

No process data is exchanged with external communication partners in the STOP_ERROR

state. No process data is transferred to the process module.