Replacement and Compatibility
An X‑COM 01 E module has more memory capacity than an X-COM 01 module. This is a
prerequisite for new protocols such as the PROFINET IO Controller V2.4+.
An X‑COM 01 E module can replace an X-COM 01 module installed in an existing system. To
ensure compatibility, observe the following points:
▪ The new X-COM 01 E module must be equipped with the same fieldbus submodules used
for the X-COM 01 module to replace.
▪ The X-COM 01 E operating system supports all protocols that were operated in the X-COM
01 module. Exception: PROFINET IO Controller V2.2. see Chapter 3.1.1.
▪ The existing X-CB 001 02 connector board can continue to be used with an X‑COM 01 E
module for all protocols. Exception: PROFINET IO Controller V2.4+.
▪ When using the PROFINET IO Controller V2.4+ protocol, the X-CB 001 04 connector board
is to be used instead of the X-CB 001 02 connector board.
Downgrade
If the PROFINET IO V2.2 protocol is to be used in an X‑COM 01 E module, then downgrade the
X‑COM 01 E module to an X-COM 01 operating system ≤ V14.12.
Refer to the maintenance manual for details on how to load operating systems.