Installation
The Transmitter Barrier is typically installed in the processing
cabinet in control room. The DZ-110/U is equipped with blue
coloured terminals 4 and 5/6 for connection of the intrinsically
safe circuit in hazardous area. Terminals 2 and 3 connects the
Transmitter Barrier to an analogue input channel in the moni
toring system. The Transmitter Barrier shall be grounded to the
Intrinsically Safe busbar in the system (6), by minimum a 1.5
mm2 cable.
The DZ-110/U snaps to a TS-32 or a TS-35 mounting rail (ac
cording to DIN46277). End stoppers shall be used to support
the units.
Safety instruction:
For safety instruction see the document 373874 K-Gauge Ex I
Safety instructions.
FEATURES
• Intrinsically safe connection of 4 – 20 mA transmitters to safe
area
• Snap-on installation to DIN rail (TS-32 or TS-35)
• Small size
• ATEX, IECEx and type approved