Features
• 40 Triple Modular Redundant (TMR) output points per Module.
• Comprehensive, automatic diagnostics and self-test.
• Automatic line monitoring per point to detect open circuit and short
circuit field wiring and load faults.
• 2500V impulse withstand opto/galvanic isolation barrier.
• Automatic overcurrent protection (per channel), no external fuses
required.
• Onboard Sequence of Events (SOE) reporting with 1 ms resolution.
• Module can be hot-replaced online using dedicated Companion
(adjacent) Slot or SmartSlot (one spare slot for many Modules)
configurations.
• Front Panel output status light-emitting diodes (LEDs) for each point
indicate output status and field wiring faults.
• Front Panel Module status LEDs indicate Module health and
operational mode (Active, Standby, Educated).
• TϋV Certified IEC 61508 SIL 3.
• Outputs are powered in isolated groups of eight. Each such group is a
Power Group (PG).