The MTL4851 and MTL4852 modules can also be located on HTP
SC16x termination boards for general purpose applications. HART loops
are simply wired through these HART Termination Panels and may be
grounded or floating circuits. The HTP boards offer a compact and cost
effective solution for general applications. CPH-SC16x backplanes are
ideal for signal loops requiring intrinsic safety (IS) protection, combining
multiplexer and IS isolator mounting. This offers considerable simplification
in wiring when compared to DIN-rail based solutions.
The HCU16 HART units connect to 16 general purpose field instruments
while maintaining channel to channel isolation. Resistor conditioning
options are compatible with all types of I/O cards. It allows pass-through
connections for transmitter power supply, input signal and common.
The HCU16AO unit includes HART filters for use with I/O cards that are
incompatible with HART communication signals.
Customised backplanes and connection units are available to provide
direct connection from DCS I/O cables, replacing the standard termination
boards.