Fieldbus standards require buses to be terminated at both ends to prevent
signal reflections. In many applications, one terminator is built into the
power conditioner, which is usually located near the control system.
The second terminator is either integrated into the Megablock or fieldbus
barrier wiring component, or added in the form of a separate DIN-rail
mounted unit.
The Crouse-Hinds series MTL range of fieldbus terminators are ideally suited
to provide the terminator that is normally installed in a junction box in the
field (along with a Megablock for interconnecting devices).
A large “T” is placed on all terminator labels for easy identification of the
Terminator location.
Design features
• Terminators are clearly marked with a large ‘T’ making them easy to identify in the field
• Provides some differential and common-mode (cable shield) over voltage protection
• The ground connection on the filedbus terminators are used to shunt any surge currents
that may get on the cable shield to a local ground in the junction box.
Although the normal practice is to ground the cable shield in the control room, this additional
ground connection will not cause ground loops.
• In the event of an overvoltage on the cable shield, a gas discharge tube fires and shunts
this unwanted current to ground