Description
The TMR 24 Vdc Digital Output Module is a member of the Trusted range of
input/output (I/O) Modules. All Trusted I/O Modules share common
functionality and form. At the most general level, all I/O Modules interface to
the Inter-Module Bus (IMB) which provides power and allows communication
with the TMR Processor. In addition, all Modules have a field interface that is
used to connect to Module-specific signals in the field. All Modules are Triple
Modular Redundant (TMR).
All High Integrity I/O Modules are made up of four sections: Host Interface
Unit (HIU), the Field Interface Unit (FIU), the Field Termination Unit (FTU),
and the Front Panel Unit (or FPU).
Field Termination Unit (FTU)
The Field Termination Unit (FTU) is the section of the I/O Module that
connects all three FIUs to a single field interface. The FTU provides the Group
Fail-Safe Switches and passive components necessary for signal conditioning,
overvoltage protection, and EMI/RFI filtering. When installed in a Trusted
Controller or Expander Chassis, the FTU field connector interconnects to the
Field I/O Cable Assembly attached at the rear of the Chassis.
The SmartSlot link is passed from the HIU to the field connections via the
FTU. These signals go directly to the field connector and maintain isolation
from the I/O signals on the FTU. The SmartSlot link is the intelligent
connection between Active and Standby Modules for coordination during
Module replacement.