The F80x module provides galvanic isolation between the
24V DC input power and the fieldbus segments, as required by
the IEC61158-2 fieldbus standard and the Fieldbus Foundation™
FF-831 validation test for power conditioners. There is also galvanic
isolation between the fieldbus segments, thereby preventing multiple
segment failures from ground faults on more than one segment. Each
segment has its own fieldbus power conditioner and current limitation.
Termination of the fieldbus segment is automatically maintained when
single or redundant F80x modules are fitted.
An F809F-Plus diagnostic module may optionally be installed on the
carrier, to automatically collect and distribute diagnostic information on
each of the eight fieldbus segments. Measured parameters may be
viewed in the Foxboro control system by either assigning the F809F
Plus as a fieldbus device to segment 1 or 8 of the powered segments,
or by means of a separate fieldbus segment. Connections for the
separate segment are provided on the baseplate. For more information
see the F809F-Plus product specification.