The F80x module provides galvanic isolation between the

24V DC input power and the fieldbus segments, as required by

the IEC61158-2 fieldbus standard and the Fieldbus Foundation™

FF-831 validation test for power conditioners. There is also galvanic

isolation between the fieldbus segments, thereby preventing multiple

segment failures from ground faults on more than one segment. Each

segment has its own fieldbus power conditioner and current limitation.

Termination of the fieldbus segment is automatically maintained when

single or redundant F80x modules are fitted.

An F809F-Plus diagnostic module may optionally be installed on the

carrier, to automatically collect and distribute diagnostic information on

each of the eight fieldbus segments. Measured parameters may be

viewed in the Foxboro control system by either assigning the F809F

Plus as a fieldbus device to segment 1 or 8 of the powered segments,

or by means of a separate fieldbus segment. Connections for the

separate segment are provided on the baseplate. For more information

see the F809F-Plus product specification.