Start-up operation
For applications requiring unattended operation, the 1336 PLUS II can resume operation when power is
restored after a power failure.
If the Power On Run feature is activated and the input power supply is disconnected, then when the
power is restored
The drive will automatically restart and run at the current commanded speed if all the necessary signals
(Enable, Auxiliary, No Stop and Start) are present.
4-20mA Current Loss Option
Many control systems will issue a 4-20mA control signal for the drive to use as a speed reference.
The drive will run at the lowest speed with the 4mA signal and at the highest speed with the 20mA signal.
The drive can also invert this signal to run the minimum speed at 20mA and the maximum speed at 4mA.
Since a minimum signal of 4mA is required, the drive must have a ‘fallback’ command
in the event of signal loss (sensor failure or disconnection).
The 1336 PLUS II includes a ‘Loss Selection’ parameter that provides five choices for signal failure modes.
1. stop the drive and signal a fault.
2. Go to minimum speed and issue a warning.
3. Go to maximum speed and issue a warning.
4. Maintain speed and issue a warning.
5. reaches preset speed and warns.
Related Product Recommendations:
1336-SN-SP1A
1336-SN-SP1B
1336-SN-SP21A
1336-QOUT-SP5A
1336-QOUT-SP6A
1336-QOUT-SP8A
1336-QOUT-SP12B
1336-QoUT-SP13A
1336-QOUT-SP14A
1336-QOUT-SP18A
1336-FEET-SP8A
1336-FEET-SP5A
1336-FEET-SP6A
1336-MOv-SP1A
1336-Mov-sP3A
1336-R2-SP2A
1336-R2-SP1A
1336-RLOAD-SP2A
1336-RLOAD-SP3A
1336-RLOAD-SP4A
1336-RLOAD-SP5B
1336-STDOFF-SP1A
1336-SCREW-sP3A
1336-BDBMX3-SP60A
1336-BDBMX3-SP24A
Leave a comment
Your email address will not be published. Required fields are marked *