Minimizing Interference
from Radiated Electrical
Noise
Important: Signals in this type of control system are very susceptible
to radiated electrical noise. The module is designed to set the loss-ofsensor
bit I:e.0/8 and the LDT-error bit I:e.0/0 when it detects position
values that are lost or corrupted by electrical noise.
Connect module output terminals to output devices with correct bonding:
• connect power supply output commons together
• electrically isolate power supply output commons from earth ground
• use bond wires that are equal in size to signal wires
Minimize interference from radiated electrical noise with correct
shielding and grounding:
• connect all of the following to earth ground:
– LDT flange, frame, and machine
– I/O chassis
– protective ground
– AC ground
– cable shields at one end only, preferably with 3/8” braid wire
(for analog output, ±15V dc PS, 24V dc PS, and LDT)
– terminal 4 of the input terminal block
• run shielded cables only in low-voltage conduit
• place the SLC-500 processor, power supply, and I/O chassis
assembly in a suitable enclosure