DIO System Overview

The DIO system consists of an SLC processor, a scanner, an Isolated Coupler

and I/O blocks. These devices form the DIO System when they are properly

connected to the DIO Link and the DH–485 Data Link as shown below. The

DIO Link and the DH–485 Data Link are independent networks.

The DIO Link consists of the scanner and I/O blocks. It enables the SLC

processor to exchange input and output information with up to 30 I/O blocks.

Output data is transferred from the SLC processor to the scanner, which then

transmits the data to the appropriate I/O block via the DIO Link. The

scanner receives input data from the I/O blocks via the DIO Link. The

scanner then provides this data to the SLC processor. The maximum length

of the DIO Link is 2,500 feet (762 meters) using Belden 9463 cable.

The SLC processor and programming devices communicate using the

DH–485 Data Link. The DH–485 port located on each I/O block allows

remote programming and/or monitoring of the SLC processor. It does not

directly control the I/O block.

Connecting a programming device to any I/O block programming port allows

the programming device to communicate with the SLC processor. The

maximum length of the DH–485 Data Link is 4,000 feet (1,219 meters) using

Belden 9842 cable.