Encoder Interface
The Ultra5000 main encoder feedback connector is CN2. The motor encoder
interface circuitry features include:
• 2.5 MHz maximum line frequency
• RS-485 serial channel for communicating with intelligent encoders
• Hall input for start-up commutation only
• Interpolation of sine/cosine encoders
All encoder signals are filtered using analog and digital filtering. The inputs
also include illegal state change detection. Refer to Figure 2.5 for a schematic
of the motor encoder inputs.
Hardware latches can be used for latching the encoder position based on an
index input or a digital input transition.