Features
• A protection, control, and monitoring IED with extensive functional library and configuration
possibilities and expandable hardware design to meet specific user requirements
• For power transformers, autotransformers, shunt reactors, T-protection, generator transformer
blocks, phase shifting transformers and small busbar systems
• For two- and three-winding transformers with up to six stabilized inputs
• For multi- or single-breaker arrangements
• Transformer differential protection with:
– Percentage bias restraint for through faults
– Waveform and Second harmonic restraint for transformer inrush
– Fifth harmonic restraint for overexcitation
– High sensitivity for interturn faults
• Restricted earth fault protection for all direct or low impedance earthed windings
– Extremely fast operation
– High sensitivity
– High and low impedance based
• Full scheme phase-to-phase and phase-to-earth distance protection with up to five zones:
– Load encroachment feature
• Instantaneous high speed short circuit function with low transient overreach
• Directional overcurrent protection with four steps for each winding
– Each step can be inverse or definite time delayed
– Each step can be directional or non-directional
• Instantaneous high speed earth fault function with low transient overreach
• Directional earth fault protection with four stages for each winding
– Each step can be inverse or definite time delayed
– Each step can be directional or non-directional
– Each step can be blocked on second harmonic component
• Synchrocheck function for single- or multi-breaker arrangements:
– Selectable energizing direction
– Two functions with built-in voltage selection
• Selectable additional software functions such as
breaker failure protection for each breaker, voltage protection, overexcitation protection, control and monitoring
• Tripping from Buchholtz, temperature devices etc. through binary inputs stabilized against capacitive discharges
• Built-in data communication modules for station bus IEC 61850-8-1
• Data communication modules for station bus IEC 60870-5-103. LON and SPA
• Integrated disturbance and event recorder for up to 40 analog and 96 binary signals
• Time synchronization over IEC 61850-8-1. LON, SPA, binary input or with optional GPS module
• Analog measurements accuracy up to below 0.5% for power and 0.25% for current and voltage and with site calibration to optimize total accuracy
• Versatile local human-machine interface
• Extensive self-supervision with internal event recorder
• Six independent groups of complete setting parameters with password protection
• Powerful software PC tool for setting, disturbance evaluation and configuration
• Remote end data communication modules for C37.94 and G.703