Mounting position
Rotations in the plane of the diaphragm have a negligible
effect. A tilt from the vertical of up to 90° causes a zero
point shift of up to 0.5 kPa (5 mbar, 2 inH2O), which can be
corrected by making an appropriate zero position
adjustment. There is no effect on the measuring span.
In applications where a dynamic inclined installation is
required (e.g. naval applications with maximum vessel
inclination of +/-22.5°), the maximum error can be up to 3
mbar for 266DSH
Such error might be resulting in a deviation from the
standard accuracy with percentual magnitude depending
on the range of the selected device.
In case of non-dynamic inclined installations, this effect
can be eliminated by performing a zero calibration in the field.
Please contact ABB to assess more in details on the installation effects