Static pressure
(zero errors can be calibrated out at line pressure)
per 0.5 MPa, 5 bar or 72.5 psi (sensor A)
per 2 MPa, 20 bar or 290 psi (sensor B)
per 3.5 MPa, 35 bar or 500 psi (sensor E)
per 7 MPa, 70 bar or 1015 psi (sensor F to S)
Model 266DSH standard static
• zero error: ±0.05 % of URL for sensor F to S
±0.08 % of URL for sensor A, B and E
• span error: ±0.08 % of reading.
Model 266DSH flange mounted
per 2 MPa, 20 bar or 290 psi
• zero error: ±0.05 % of URL for sensor F to P
±0.08 % of URL for sensor E
span error: ±0.08 % of reading.