Applications

The module 560BOR01 controls 16 binary process signals via relay contacts. The output signals can be assigned to process functions according to configuration rules.

The module 560BOR01 can process the following types of signals:

– Single or double command (SCO or DCO) with 1- or 2-pole output, no checksum (n select 1).

– Single or dual commands (SCO or DCO) with 1.5 or 2-pole outputs, without checksum (1 out of n).

– Regulating step command (RCO), 1 or 2 poles

– Digital setpoint command, 8 or 16 bit, no strobe (DSO8 or DSO16)

– Digital setpoint command, 8 or 16 bit, with strobe (DSO8 or DSO16)

– Bit String Output, 1. 2. 8 or 16 bits (BSO1. BSO2. BSO8 or BSO16)

Modules allow switching voltages up to 150 V DC or up to 2 A continuous current.

Features

Binary outputs

The binary outputs utilize relay contacts.

The 16 outputs are divided into two groups. Each of the 8 outputs has a common circuit. The groups are isolated from each other and from the internal electronics.

The relay coil supply voltage (24 VDC) is switched by an www.cniacs.com internal relay (R17).

The relay coil supply voltage (24 VDC) is monitored internally before and during the command output.

Command outputs to the process equipment can be executed either directly or in conjunction with the command output monitoring module.

The command output monitoring module is responsible for checking the output circuits (1 out of n times). For more details, refer to the Command Output Monitor datasheet.