Cyberex® HPP withABB ProLine panelboards

The Cyberex HPP helps remove the electrical

concerns that come along with high density data

centers. As voltage increases on the data center

floor so does the potential for electrical dangers.

Cyberex’s HPP with current limiting branch circuit

breakers, helps mitigate the risk of arc flash and

provides the highest level of protection for IT

equipment. 

The resin encased bus design and

touch safe plug in branch breakers reduce shock

hazard and increase flexibility after installation.

Inherent coordination up to moderate fault levels

reduces risk of cascading faults keeping power to

critical loads.

•   UL listed current limiting branch circuit breakers

•   Touch safe

•   Voltage ratings: 208/120V, 415/240V, 480/277V

•   Current rating: 225A, 400A

•   1 to 25A branch breakers at 480V

•   Interrupting rating: 14kA

•   Main/branch breaker coordination up to 14kA at 480V