Bus protection via GOOSE

The IEC 61850 implementation in PCMU MSOC includes

fast peer-to-peer communication, over the substation bus.

Use GOOSE communication between PCMU MSOC relays of

the incoming and outgoing feeders of a substation to form a

stable, reliable, and high-speed busbar protection system. The

cost-effective GOOSE-based busbar protection is obtained by

configuring the relays and the operational availability of the pro

tection is assured by continuous supervision of the protection

devices and their GOOSE messaging over the station bus. No

separate hard-wiring is needed for the horizontal communica

tion between the switchgear cubicles.The breaker monitoring can

include checking the wear and tear of the circuit breaker, the

spring charging time of the breaker operating mechanism and

the gas pressure of the breaker chambers. The relay also mo

nitors the breaker travel time and the number of circuit breaker

operations to provide basic information for scheduling breaker

maintenance.