Protection functions
REB611 offers phase-segregated (three phases) high
impedance differential protection and non-directional earth
fault protection for busbars, motors and generators. The relay
also offers high-impedance differential-based restricted earth
fault protection for motors, generators, reactors and power
transformers. REB611 is ideally suited for backup protection.
Application
REB611 offers bus-differential protection in a single zone with
bus-wire supervision. It also offers the possibility for bus
differential protection over two zones using two REB611 relays.
The combined restricted earth-fault and residual earth-fault
protection functionalities of the relay enable its use in the
protection of a motor or generator. Due to the individuality of
the high-impedance protection functions, a single relay can be
used for restricted earth-fault protection of both the high and
low voltage sides of a power transformer.