Current protection
Instantaneous phase overcurrent protection (PIOC, 50)
The instantaneous three phase overcurrent function has a low transient overreach and short tripping
time to allow use as a high set short-circuit protection function, with the reach limited to less than
typical eighty percent of the power line at minimum source impedance.
Four step phase overcurrent protection (POCM, 51_67)
The four step phase overcurrent function has an inverse or definite time delay independent for each
step separately.
The single input overcurrent function has a low transient overreach and short tripping times to
allow use as a high set short circuit protection function, with the reach limited to less than typical
eighty percent of the power line at minimum source impedance. The function can be configured
to measure the residual current from the three phase current inputs or the current from a separate
current input.
Four step residual overcurrent protection (PEFM, 51N/67N)
The four step single input overcurrent function has an inverse or definite time delay independent for
each step separately.
All IEC and ANSI time delayed characteristics are available together with an optional user
defined characteristic.