Requirements
To ensure correct and safe operation of the relays, it is recommended that preventive
maintenance be carried out every five years on relays operating under specified conditions;
See table 4.1.-1 and section 5.2.4. Technical Data.
When used for real-time clock or logging data functions, the batteries should be replaced every five years.
Configuration
By appropriately configuring the output contact matrix, signals from the protection
level can be used as contact functions. The start signals can be used for
for blocking cooperating relays and for signaling.
The following figure shows the default configuration of the relay: all trip signals are routed to trip the circuit breaker.
In the first example in Figure 4.2.-1. the residual current is measured by
the iron core balancing current transformer and the output contacts are connected to enable the automatic reclosing function.
In the second example in Figure 4.2.-2. the residual current is measured through
the trimming connection of the phase current transformer and the output contacts are connected
to enable the trip lockout function with an external reset switch.