Application
RET630 has been designed to be the main
protection and offer full protection for
two-winding power transformers. The
comprehensive transformer management
relay offers two predefined configurations,
of which one is intended for two-winding, high
and medium-voltage (HV/MV) transformer
applications not requiring restricted earth-fault
protection, and the other for such applications
requiring it.
Hot spot and aging rate monitoring is
introduced, which allows calculating the hot
spot temperature of the transformer winding
and the momentary aging rate. As a result,
the impact of thermal stress on the lifetime
of the transformer can be determined.
RET630 also features an integrated voltage
regulator. The voltage regulator allows automatic
and manual voltage regulation of power
transformers with a motor-driven on-load
tap changer.
An optional RTD/mA module offers eight analog
RTD or mA measuring inputs and four mA
outputs. The RTD and mA inputs can be used for
measuring the oil temperature at the bottom and
top of the transformer tank and the ambient
temperature, thus extending the functionality of
the thermal overload protection and preventing
premature aging of the transformer windings.