The relay also supports IEC 61850 process bus concept by
sending and receiving sampled values of currents and voltages.
With this functionality the galvanic interpanel wiring can be
replaced with Ethernet communication. The analog values are
transferred as sampled values using the IEC 61850-9-2 LE
protocol. REX640 supports publishing of one and subscribing
of four sampled value streams. The intended application for
sampled values are current-based differential protection
functions or sharing the voltage values with the relays that have
voltage-based protection or supervision functions. The relay
can receive up to four sampled value streams and totally 16
measurements can be connected into the protection relay
application.
In PRP, each network node is attached to two independent
networks operated in parallel. The networks are completely
separated to ensure failure independence and can have
different topologies. As the networks operate in parallel, they
provide zero-time recovery and continuous checking of
redundancy to avoid failures.