DNP3 supports both serial and TCP modes for the connection
of up to five masters. Changing the active setting and reading
fault records are supported. DNP serial and DNP TCP can be
used in parallel. If required, both IEC 61850 and DNP can be run
simultaneously.
The relay supports Profibus DPV1 with support of SPA-ZC 302
Profibus adapter. If Profibus is required, the relay must be
ordered with Modbus serial options. Modbus implementation
includes SPA protocol emulation functionality. This functionality
enables connection to SPA-ZC 302.
When the relay uses the RS-485 bus for the serial
communication, both two- and four-wire connections are
supported. Termination and pull-up/down resistors can be
configured with DIP switch on the communication card so that
external resistors are not needed.