Recorded data
The relay can store the records of the latest 128 fault events.
The records can be used to analyze the power system events.
Each record includes, for example, current, voltage and angle
values and a time stamp. The fault recording can be triggered
by the start or the trip signal of a protection block, or by both.
The available measurement modes include DFT, RMS and
peak-to-peak. Fault records store relay measurement values
when any protection function starts. In addition, the maximum
demand current with time stamp is separately recorded. The
records are stored in the nonvolatile memory.
Load profile
The load profile recorder stores the historical load data
captured periodically (demand interval). Up to 12 load
quantities can be selected for recording and storing in the
nonvolatile memory. The recordable quantities include
currents, voltages, power and power factor values. The
recording time depends on a settable demand interval
parameter and the amount of quantities selected. The
quantities’ type and amount to be recorded are determined in
the application configuration. The recorded quantities are
stored in the COMTRADE format.