The following five option cards are available:
• The Fibre-Optic Option Card SFIBER pro vides three fibre-optic transceiver pairs for
the interconnection of bay level devices,connection between two RER 111 modules
equipped with Fibre-Optic Option Cards or between a RER 111 module and higher
level devices e.g. MicroSCADA.
• The RS-485 Option Card SRS485 provides a means of connecting LON bus
devices using the RS-485 interface to the LonWorks network. The card also com
prises a fibre-optic transceiver pair.
• The SLTA Option Card SSLTA provides the interconnection between higher level
devices (e.g. monitoring terminals, PC, etc.) and the LonWorks network.
It can also provide the interconnection between RER 111 modules by using the fibre-optic
transceiver pair.
• The Router Option Card, SROUT, provides connection to devices using twisted
pair (TP/XF-78 or TP/XF-1250) transceiv ers and / or using fibre-optic transceiver
pairs. It also provides a means by which an overall system can be divided into multiple
subsystems.
• The Double Connection Option Card SREDU provides a means for connecting
devices together by using double connec tions. This method enables the use of two
fibre-optic transceiver pairs to connect to any device supporting double connection.
In the event of a fault in one fibre-optic connection, this connection is still able to
receive and transmit data to devices.
• The LON Clock Master option card SLCM provides means for connection to a clock
reference device and performs time synchronization on LON.There are five sepa
rate time synchronization methods for different types of bay level devices and for
different accuracy requirements. The SLCM option card includes an internal
clock to generate various synchronization messages and signals in order to synchro
nize other devices on the LON network.