REX640 includes two autoreclosing functions, each with up to
five programmable autoreclosing shots of desired type and
duration. A load-shedding function performs load shedding
based on underfrequency and the rate of change of the
frequency.
To validate correct closing conditions for a circuit breaker,
REX640 contains a synchrocheck function. For installations
including synchronous generators, REX640 introduces a
synchronizer that actively controls the generator’s voltage and
frequency in order to reach a synchronous situation across the
circuit breaker. The synchronizer functionality is available for a
generator circuit breaker as well as for a non-generator
(network) circuit breaker. A complete installation-wide
synchronizing system can be built using the REX640 relays. The
maximum size of the synchronizing system is eight generator
breakers and 17 non-generator breakers.