Synchronization of a generator circuit breaker can be

implemented using a single REX640 relay including the

ASGCSYN function block. The relay interfaces the external

measurement and control circuitry via hardwired binary and

analog signals. The excitation and prime mover control signals

are based on pulse commands, either with fixed or variable

length. The synchronizer function block has three different

function modes: manual, semi-automatic and automatic. In

each of these modes, the LHMI acts as the local user interface.

The LHMI includes the necessary command, indication and

measurement features for each of the modes, thus rendering

the conventional dedicated synchronizing panel unnecessary.

REX640 also supports systems in which non-generator circuit

breakers are synchronized. The prerequisite is that all the

feeders within the system are equipped with REX640 relays.

The generator relays have to contain the ASGCSYN function

block and all the non-generator relays need to contain the

ASNSCSYN function block. In addition, all the REX640 relays

have to contain the coordinator function block ASCGAPC.