Disturbance recorder
The relay is provided with a disturbance recorder featuring up to
24 analog and 64 binary signal channels. The analog channels
can be set to record either the waveform or the trend of the
currents and voltages measured.
The analog channels can be set to trigger the recording function
when the measured value falls below or exceeds the set values.
The binary signal channels can be set to start a recording either
on the rising or the falling edge of the binary signal or on both.
The binary channels can be set to record external or internal
relay signals, for example, the start or trip signals of the relay
stages, or external blocking or control signals. The recorded
information is stored in a nonvolatile memory in COMTRADE
format and can be uploaded for subsequent fault analysis.