Special features of the
selective main circuit-breaker S 750
− High breaking capacity 25 kA at 230/400 V~
− High energy limitation
− Suitable to provide selective overcurrent protection
in meter boards and in main distribution frames
− Suitable for isolation of electric circuits
− Current-limiting selectivity
− Voltage independent function
− High isolation ability:
Ui = 690 V,
Uimp = 6 kV with a test voltage of 9.8 kV
Overvoltage category IV,
Pollution degree 3
− Easy assembly with screwless connection to busbars
and cables on the load side
− Input frame terminals for busbar feeding
up to 50 mm2/100 A
− Isolation function according to IEC 60364 and IEC 60664
− Additional contact position indicator
RED = ON / GREEN = OFF
− Lockable and sealable
− Can be operated by ordinary people