Features and interfaces
Terminal connections
All connections to SYMAP® are made with terminal plugs on the back of
the device, allowing the device to be exchanged easily.
Analog input for measurement
SYMAP® provides inputs for analog sensors at the rear of the device. If
terminal plugs for the CTs are disconnected, the circuits will be linked
automatically so there is no disconnection in the CT circuit loops.
A total of 17 analog inputs for current and voltage transformers are used
for protection functions. The following list shows possible connections
for current transformers (CT) and potential transformers (PT):
• 3 x CT inputs for feeder current
• 1 x CT input for ground current
• 3 x PT inputs for feeder voltage
• 3 x PT inputs for 1st bus bar voltage
• 3 x PT inputs for 2nd bus bar voltage
• 1 x PT input for ground voltage