Networkable via PC-based software packages
Flame Explorer™ or PROFIBUS Device Type Manager (DTM)
Applications
– Utility and industrial boilers (wall burners, angle burners, make-up WHRB burners, downdraft burners and cyclone burner types)
– Process heaters
– Sulphur recovery
– Gas turbines
– Offshore boiler and furnace installations (stainless steel housing (AISI 316L))
Multiple fuels
– Natural gas, coke oven gas and sulphur gas
– Light and heavy fuel oil
– Emulsions
– Pulverised coal
– Biomass
Characteristics
Operation
– UV, Visible, Infrared Solid State Sensor
– Dual sensor UVIR
– Continuous self-test
– Fast Flame Failure Response Time (F-FFRT)
– Digital input for remote setup (isolated)
– Automatic adjustment
Safety, communication and signalling
– Redundant Profibus DP-V1 (isolated)
– Redundant Modbus (isolated)
– 4-20 mA (isolated)
– Fail-safe flame relay N.O. contact
– Fail-safe relay N.O. contact
– Real-time flame flicker frequency display
– Real-time flame intensity display
– Real-time flame quality display
– Rejection of power frequency and artificial lighting (EN298 compliant)
Complete Safety Instrumented System (SIS) solutions for boiler and plant protection
– Symphony Plus TÜV-certified safety systems include SIL 2 and SIL 3 rated field instrumentation, including SF810i flame scanners, controllers, I/O modules, valve positioners and actuators
– Delivered and supported to the most stringent standards including IEC 61508. EN-230. EN-298. NFPA 72 and NFPA 85
PROFIBUS communication interface
UvisorTM SF810i modules are fully integrated via www.cniacs.com the built-in convenient PROFIBUS DP interface. The main features of the interface are as follows
– DP/V1 communication standard
– Communication rates up to 12 MBd
– Compliance with PROFIBUS PNO slave specification
– System (master) redundancy
– Flight (line) redundancy
– 2 independent PROFIBUS slave hardware interfaces per module
– DTM and GSD files available
PROFIBUS interface for exchanging parameters, commands, and process variables with the Symphony Plus controller, eliminating the need for locally adjusted jumpers or switches.
Configuration
– Flame Explorer™ monitoring and configuration tool Proprietary PC-based software package running on Windows operating systems
– Local pushbutton and numeric displays
– Firmware download tool
– Automatic tuning