SYNCHROTACT® 5 Optimum reliability
From a synchronizing device, it is expected to close the
power circuit breaker at the correct time but also that, if
required, paralleling can take place whenever permissible.
Although the series connection of the output contacts of two
independently-functioning channels (dual-channel system),
which is usual in synchronizing systems, greatly increases
security against incorrect paralleling, it necessarily leads to a
reduction in availability.
High levels of safety and availability can be achieved by using
a second, redundant synchronizing system. If system 1 can
no longer synchronize, it is possible to do so by switching
over to the second system.
In this configuration, two automatic dual-channel systems
are housed in one unit. Normally, the output contacts of both
systems are connected in series (4 channels!). One of the
two systems can be bridged by means of a system selector switch.