SYNCHROTACT® 5
Range of applications
Synchronizing devices are widely used in power stations or
industrial installations with their own power generating facilities,
where the generators need to be paralleled with an island line
or a public line, or in power distribution systems.
Power circuit breakers may only be closed if both voltages are
approximately synchronous (coincident). Otherwise, faults in
line operation, loading of the generators and, in extreme cases,
damage to the generators can result.
SYNCHROTACT® 5 performs these functions safely and reliably,
whether as a monitoring element for manual paralleling or as
an independent fully-automatic synchronizing device.
Command generation
The command generation calculates the necessary lead angle
αv, by which the paralleling command must be advanced
due to closing time delay. The action ensures that the main
contacts close at precisely the right time. If α reaches αv at
the same time as paralleling release (CHK RELEASE), the
command is issued. Under synchronous conditions, ie,
permanent paralleling release during the adjustable monitoring
time, tsup, the CMD is also issued without taking the lead
angle into consideration.