Digital output
The alarms generated in the positioner can be polled via the
digital output as a collective alarm.
The desired information can be selected via the operator panel
or remotely via the configuration program.
The output can be set to “active high” or “active low”, as
required.
Digital input
For the digital input, one of the following safety options can be
selected. You may use the operator’s panel or configuration
program to select an option.
— No function (default)
— Move to 0 % position
— Move to 100 % position
— Hold previous position
— Disable local configuration
— Disable local configuration and operation
— Disable any access (no local or remote access via a PC)
The selected function is activated when the 24 V signal is no
longer connected to the digital input (< 11 V DC).