Switching points for the position

You can use these parameters to define two position limits for

signaling (see option “Module for digital position feedback”).

Digital output

The alarms generated in the positioner can be polled via the

digital output as a collective alarm.

The desired information can be selected via the operator panel

or remotely via the configuration program.

The output can be set to “active high” or “active low”, as required.

This parameter can be set separately for each end position.

When the respective configured limit value is exceeded, the

shut-off function causes immediate travel of the actuator until

reaching the set end position.

If the value “0” is entered for the corresponding parameter, the

position is further controlled, even in the respective end

position.