Modbus to IEC-104 conversion
ARC600 provides support for generic Modbus RTU and
Modbus TCP devices such as ABB’s RIO600. In addition,
support is also provided for the preselected Modbus
parameters for Fault Passage Indicators (FPI). Currently,
Horstmann Compass B and Kries IKI-50 are supported.
ARC600 polls the fault indicator devices, connected to the
serial port, using Modbus protocol and converts the values to
IEC 60870-5-104. Up to four fault indicators can be
connected to one device. IEC 60870-5-104 is used to
communicate towards a SCADA via the Arctic M2M Gateway
over the available customer chosen cellular data network.
IEC-101 to IEC-104 conversion
With ARC600. conventional IEC 60870-101 serial devices can
be attached to a modern TCP/IP based IEC 60870-5-104
control system. This is enabled by the protocol conversion
from IEC 60870-5-101 to IEC 60870-104. In this case,
ARC600 (IEC-101 master) uses local synchronous data
polling where it continuously sends requests and the IEC-101
device (IEC-101 slave) responds. In the direction of the
control room, the communication protocol is IEC-104 and
ARC600 can send events asynchronously as they arise while
SCADA performs only slow-period background scans.
Another advantage of the local protocol conversion is an
advanced data acknowledgement mechanism. IEC-104
allows multiple packets, and multiple events in a single
packet, to be acknowledged collectively and the packets can
be buffered up to the time of acknowledgement from SCADA.