Emerson DeltaV™ M-series I/O carriers System Compatibility

System Compatibility

M-series I/O carriers are not physically compatible with

S-series controller carriers, except when used with the

DeltaV SIS Adapter.

The M-series controllers cannot detect the difference between

an 8-wide and a 4-wide carrier. If a 4-wide carrier is used,

the four I/O slots after the slots on the carrier will be lost to

an M-series controller. If either a 4-wide or 8 wide carrier is

connected after a 4-wide carrier, the first slot number will

be 5 numbers higher than the last slot on the 4-wide carrier.

For example, if a controller has a 4-wide carrier followed by

an 8-wide carrier, the slots on the 4-wide carrier will be

1. 2. 3. and 4. and the slots on the 8-wide carrier will be

slots 9. 10. 11. 12. 13. 14. 15. 16. The PK Controller does

not have this behavior because it can distinguish between

a 4-wide and an 8-wide carrier. However, there is still a limit

of 8 total carriers (4-wides and/or 8-wides) on any controller.

The horizontal carrier family also offers a 2-wide power carrier.

Use this carrier, along with one or two system power supplies to

provide 12 V DC local bus power connected through the carrier

extenders. There are two 12 V DC output connections powered

by either supply. For redundant power, ensure that the power

demand is within the output range of one system power supply.

With the introduction of the PK controller, a 4 wide I/O carrier

is available for use with M-series I/O cards when a smaller

footprint for the hardware is required. The 4-wide carrier

allows for individual field power per card slot and is ideal

if separate field power is required for redundant I/O cards.

Emerson DeltaV™ M-series I/O Benefits

Benefits

Modular design allows flexible installation. A T- type DIN

rail is all you need to mount the power/controller carrier into

place. The I/O interface carrier plugs on to the power/controller

carrier. Simply plug your I/O terminal blocks into the carrier.

The DeltaV system’s modular design approach allows you to

add I/O carriers as you need them.

Allows you to expand online. Additional 8-wide carriers

may be added online as desired. Carrier extenders give you

the flexibility to install I/O carriers in multiple rows with 1.2.

3 or 4 carriers per row.

Integrated power distribution. Controller and I/O interface

power distribution is integrated into the carriers to reduce and

simplify power and grounding. Carriers also have integrated

shield ground bar to isolate and drain field noise away from

system power.

Emerson DeltaV™ M-series I/O Subsystem Horizontal Carriers

• Modular design allows flexible installation

• Allows you to expand online

• Integrated power distribution

Introduction

Get your I/O subsystem up and running efficiently with the

DeltaV™ horizontal mount I/O carriers. The power/controller

carrier contains internal power buses. You don’t need to use

external cabling to connect the system power supply to the

DeltaV controller and the I/O interface carriers.

The power/controller and I/O carriers are modular.

Purchase only what you need but be assured that as your

system grows you can add plug-and-play carriers—Easy!

Emerson With the introduction of DeltaV SIS the left one-wide

With the introduction of DeltaV SIS the left one-wide

and right one-wide dual carrier extenders have two,

44-pin D- Shell connectors which supports dual cables for

a fault tolerant configuration. The A and B connectors are

in parallel so either port may be used. The new dual carrier

extenders are a pre-requisite for DeltaV SIS as these also

provide extension of the redundant safety bus used by the

Safety Logic Solvers. The VerticalPLUS mount carriers also

support dual cables and can be used with DeltaV SIS.

Refer to the new VerticalPLUS Carrier Product Data Sheet

for more details on these new carriers.

The horizontal carrier family also offers a 2-wide power carrier.

Use this carrier, along with one or two system power supplies to

provide 12 V DC local bus power connected through the carrier

extenders. There are two 12 V DC output connections powered

by either supply. For redundant power, ensure that the power

demand is within the output range of one system power supply.

Emerson The I/O interface carrier plugs on to the power/controller carrier

Product Description

The I/O interface carrier plugs on to the power/controller

carrier. The power/controller carrier supplies the system

power and communications between the I/O interfaces and

the controller. The controller processes the I/O interface

information. An additional power/controller carrier is required

for use with redundant controllers.

Mount your interface carrier on a T-type DIN rail. The I/O

interface carrier includes the connections for the bulk 24 V DC

field instrument power, I/O interfaces, and terminal blocks.

Each I/O interface carrier is equipped with a connector that

allows an additional I/O interface carrier to be plugged on to it.

Up to 64 I/O interfaces on eight 8-wide I/O interface carriers are

supported by a single I/O subsystem. For the horizontal-mount

solution, 1-wide local bus extenders allow you to continue

the I/O bus on a different row of carriers. There are two types

of 8-wide I/O interface carriers available. They both have

connectors for field power on the top of the carrier. The original

carrier connects each set of field power terminals to two I/O

cards, and the other option have individual field power per card

slot and is ideal if separate field power is required for redundant

I/O cards.

ABB CI873A Ability™ System 800xA® hardware selector

 Features and benefits

 • Supports Ethernet/IP and Device Net protocols

 • Support 6 redundant pairs of CI873A from 5.1 FP4

The CI873A is an AC 800M communication interface that connects to

 external Ethernet devices using the EtherNet/IP protocol. The TP867

 Baseplate has two RJ45 Ethernet connectors, but only the CH1

 connector that supports 100Mbps is used. The CI873 expansion unit

 contains the CEX-Bus logic, a communication unit, and a DC/DC

 converter that supplies the required voltage from +24 V supply

 through the CEX-Bus.

 The CI873A module wi l only work with System 800xA 6.0.3.3, 6.1.1

 and subsequent versions. The CI873A support 6 redundant pairs of

 CI873A from 5.1 FP4.

ABB DIS880 Ability™ System 800xA® hardware selector

Select I/O is an Ethernet networked, single-channel granular I/O system for the

ABB Ability™ System 800xA automation platform.Select I/O helps decouple project tasks,

minimizes the impact of late changes, and supports standardization of I/O cabinetry

ensuring automation projects are delivered on time and underbudget. A Signal Conditioning

Module (SCM) performs the necessary signal conditioning and powering of the connected field

device for one I/O channel.

The DIS880 is a Digital Input 24V Signal Conditioning Module for use in High Integrity applications

(certified for SIL3) supporting 2/3/4-wire devices with Sequence of Events (SOE).

ABB DIS880 Features and benefits

Features and benefits

• Digital input for 2-wire, 3-wire and externally powered 4-wire field devices

• Can be used in hazardous areas

• Field device power output current limited to 30 mA

• Channel to channel galvanic isolation

• Configurable software signal filter 0…100 ms

• Protected against wrong wiring

• Diagnostics:

– Loop supervision (open circuit and short circuit)

– Hardware error supervision

– Communication supervision

– Internal power supervision

• Sequence of Events (SoE)

• DIS880 supports both Normally Open (NO) and Normally Closed (NC) 24 V loops and both will

confirm to SIL3.

• Single loop granularity – each SCM handles a single channel

• Supports hot swap

• Mechanical locking slider which turns off field device power and/or output before removal

• Field disconnect function which can galvanically separate the field loop wiring from the SCM during

commissioning and maintenance

• All SCMs have electronic current limitation

• Mechanical keying to prevent insertion of wrong module type after commissioning

• 24V DC powered through Modulebus

• Configurable through parameters

• LED indicators on the SCM indicate the operational state of the module

• Certified for SIL3

ABB CI920AN (CIPBA) Ability™ System 800xA® hardware selector

The remote S900 I/O system can be installed in non-hazardous

areas or directly in Zone 1 or Zone 2 hazardous area depending on

the selected system variant. S900 I/O communicates with the

control system level using the PROFIBUS DP standard. The I/O

system can be installed directly in the field, therefore the costs for

marshalling and wiring are reduced.

The system is sturdy, error-tolerant and easy to service. Integrated

disconnection mechanisms allow replacement during operation,

meaning that there is no need to interrupt the primary voltage in

order to exchange the power supply units.

S900 I/O type N. For installation in safe (= non-hazardous) area.

CI920AN Communication Interface V 2.1 (CIPBA), for Fieldbus

protocol PROFIBUS DP-V1 (IEC 61158). Use only CI920AN with the

same firmware for redundancy for PROFIBUS DP-V1 (observe

Release Notes).

ABB CI920AN (CIPBA) Features and benefits

Features and benefits

• Redundancy (Power and Communication)

• Hot Configuration in Run

• Hot Swap functionality

• Extended Diagnostic

• Excellent configuration and diagnostics via FDT/DTM

• G3-coating for all components

• Simplified maintenance with auto-diagnostics

• Fieldbus protocol PROFIBUS DP-V1 (IEC 61158)

• Coupling of the internal CAN bus to external PROFIBUS

• HART over PROFIBUS DP-V1

• Line or media redundancy via two coupling modules

• Electrical isolation between fieldbus, power

• Diagnosis, configuration and parameterization via PROFIBUS