Relay modules may be programed to actuate based on
alarm conditions defined in other modules. Use standard
logic elements (True AND, Normal AND, OR and NOT) to
combine various alarms and statuses (e.g. OK statuses,
Bypass, Protection State, Inhibit, Attention, Protection Fault,
etc.) into relay activation conditions. Orbit Studio is used to
program the voting logic.
Relays can operate as a system or group protection fault
relay, if programmed to do so, especially when the protection
fault relay on the SIM does not provide adequate granularity
of system health – typically for multiple machines in one system.
Pairs of relays within the module function as a single Double
Pole, Double-Throw relay when appropriately configured.
Both relay types are available for SIL system implementation.
See Orbit 60 SIL User Guide (134M0398) for additional details
and design considerations.