Basler Electric AEC63-7 Overexcitation Shutdown
Overexcitation Shutdown
Overexcitation detection provides a single-pole solid-state
contact closure across terminals A1 and A2. should the
regulator output voltage exceed 65 Vdc ±2 Vdc for a
sufficient time. For voltage above 105 Vdc ±5 Vdc, there is
a second (shorter) inverse time curve. The total inverse
time delay curve is shown in Figure 2.
After the overexcitation solid-state contact has been
made, the regulator overexcitation circuit can be reset by
decreasing the supply voltage on terminals 3 and 4 to less
than 6 Vac for a minimum of 2 seconds. This may be
accomplished by stopping the prime mover or interrupting
the regulator input by means of a reset switch. In cases
where the generator is operating in parallel mode, it may
not be desirable to allow the regulator alone to shut down
which may cause the generator to be motored. However,
continuous operation at output currents greater than the
continuous rating after the overexcitation contact has been
made may result in failure of the ac supply fuse or may
eventually cause regulator failure. If this kind of operation
will take place, an alternative external means should be
employed to protect the system.
A1 and A2 are optically isolated and floating. Any supply,
12 to 250 Vac or dc may be used, provided that current is
limited to 150 mA. Use of a dc supply to terminals A1 and
A2 will cause the solid-state device to latch after tripping.
In this case, the supply must also be removed to unlatch
the device.