Bently Nevada ORBIT 60 SERIES External Display System

Display Placement

Expensive KVM Extenders are not needed to place displays far

away from Orbit 60  installation locations. Since the Orbit

Display connects to Orbit 60 chassis via standard Ethernet

network connections, the Orbit 60 Display system can be

placed anywhere your Ethernet network infrastructure

supports. The display location is only limited by security and

network infrastructure necessary to support Orbit Display.

It is possible to place Orbit Display in a variety of locations:

• Physically adjacent to Orbit 60 chassis

• Next to the machines being monitored

• In a local or remote control room

The Orbit Display system includes your choice of display

screen, an industrial computer with a customized operating

system, and software that communicates with one or more

Orbit 60 systems. The system can be certified for hazardous

locations. Condition monitoring data is communicated to

external displays via a Display Port or VGA connection.

Bently Nevada ORBIT 60 SERIES Orbit Display

Orbit Display

The Orbit Display system includes your choice of display

screen, an industrial computer with a customized operating

system, and software that communicates with one or more

Orbit 60 systems. The system can be certified for hazardous

locations. Condition monitoring data is communicated to

external displays via a Display Port or VGA connection.

Touchscreen connection can use USB or Serial connection.

The Orbit Display shows Orbit 60 machinery protection

system information such as:

• Direct measurements

• 1X measurements

• Gap measurements

• Measurement alarms

• System event list

• Alarm event list

The standard tabs show direct measurements, 1x filtered

vibration measurements, gap values, and other trended

variables.

Bently ORBIT 60 SERIES Electromechanical Relay (EMR)

Electromechanical Relay (EMR)

This relay drives a load directly, or through, an interposing

relay. This module takes two slots. It features 8 Epoxy Sealed,

Single-Pole Double-Throw Electromechanical Relays. This

module supports an AC voltage range of 5-250 Vac for loads

of 100 mA to 4 A. The module also supports DC voltages and

loads of 5-30 Vdc at 4 A.

Solid State Relay (SSR)

This relay connects to an external system’s discrete input for

low current communication. It occupies a single slot and

features 8 Solid-State Relays. This module supports

secondary voltages from 1 Vdc up to 125 Vdc

and loads of 0.01 to 125 mA.

Bently Nevada ORBIT 60 SERIES Relay Modules

Description

Relay modules may be programed to actuate based on

alarm conditions defined in other modules.  Use standard

logic elements (True AND, Normal AND, OR and NOT) to

combine various alarms and statuses (e.g. OK statuses,

Bypass, Protection State, Inhibit, Attention, Protection Fault,

etc.) into relay activation conditions. Orbit Studio is used to

program the voting logic.

Relays can operate as a  system or group protection fault

relay, if programmed to do so, especially when the protection

fault relay on the SIM does not provide adequate granularity

of system health – typically for multiple machines in one system.

Pairs of relays within the module function as a single Double

Pole, Double-Throw relay when appropriately configured.

Both relay types are available for SIL system implementation.

See Orbit 60 SIL User Guide (134M0398) for additional details

and design considerations.

Bently Nevada ORBIT 60 SERIES Recorder Output Module ROM

The recorder output module provides analog outputs for any

proportional signal measurements available within the Orbit

60 system including the following examples:

• Processed Vibration measurements (Direct, 1X

Amplitude, 1X Phase, etc.)

• Temperature measurements

• Position measurements

The recorder output channels’ configuration includes several

options for clamp output levels, providing an indication of an

invalid health status of the associated measurement. The

system will also attempt to output the configured clamp

signal when any fault within the Recorder

Output channel or output load is detected.

The configuration also includes the option to

include Recorder Output channels within the

protection path so that detected faults within

the Recorder module or wiring can be

annunciated through Protection Fault relays.

(See SIL User Guide 134M0398 for additional

details when using the Recorder Output channels in a SIL application.)

Bently Nevada Recorder Output Module is a 8-channel single slot width module

The recorder output module provides analog outputs for any

proportional signal measurements available within the Orbit

60 system including the following examples:

• Processed Vibration measurements (Direct, 1X

Amplitude, 1X Phase, etc.)

• Temperature measurements

• Position measurements

The recorder output channels’ configuration includes several

options for clamp output levels, providing an indication of an

invalid health status of the associated measurement. The

system will also attempt to output the configured clamp

signal when any fault within the Recorder

Output channel or output load is detected.

The configuration also includes the option to

include Recorder Output channels within the

protection path so that detected faults within

the Recorder module or wiring can be

annunciated through Protection Fault relays.

(See SIL User Guide 134M0398 for additional

details when using the Recorder Output

channels in a SIL application.)

Bently Nevada ORBIT 60 SERIES Recorder Output Module

Description

The recorder output module is a 8-channel single slot width

module that provides an analog output signal based on a

processed measurement from any of the proportional

measurements within  the system. The output of the recorder

output channel is proportional to the associated

measurement value within the measurement’s full scale range.

The recorder output module is software-selectable to

operate in several output modes, providing the following

analog output signal ranges:

• 4 to 20 mA

• 1 to 5 V

• 0 to 10 V

When configured for a 4-20 mA output, the recorder channel

supports the extended output range of 3.8 mA to 20.5 mA to

align with the NAMUR NE43 standard.

These differing signal ranges can accommodate

connections to various interfacing equipment designed to

consume and interpret the proportional analog signals.

The recorder output module provides analog outputs for any

proportional signal measurements available within the Orbit

60 system including the following examples:

• Processed Vibration measurements (Direct, 1X

Amplitude, 1X Phase, etc.)

• Temperature measurements

• Position measurements

Bently Nevada ORBIT 60 SERIES Process Variable and Discrete Input Module

The monitor accepts +4 to +20 mA current inputs or any

proportional voltage inputs between -10 Vdc and +10 Vdc, in

addition to monitoring “dry” or “wet” contacts which can be a

sensor, switch, or relay.

Primary purposes of the PVD Module:

• Continuously process input from monitored

parameters to be compared against configured alarm

setpoints to drive alarms for machinery protection.

• Allow provision of essential machine information, such

as Trip Multiply for machine startup and Alarm Inhibit

for both operations and maintenance personnel.

These modules occupy a single slot. The module OK LEDs

indicate proper functioning and the LINK LEDs indicate good

system communication. Six Channel Status LEDs on the utility

side of the module indicate a connected sensor in OK condition.

Bently Nevada Orbit 60 Series Isolated Process Variable

Description

The Orbit 60 Series Isolated Process Variable and Discrete

(PVD) Input module processes machine-critical parameters

such as pressure, flow, temperature, and levels that merit

continuous monitoring. The module conditions and digitizes

the signals so the result can be compared with user

programmable alarm setpoints. The user can program the

PVD module using the Orbit Configuration software to

perform current, voltage or discrete input measurements.

This module provides discrete inputs for essential operational

commands, such as Trip Multiply for machine start-up and

Alarm Inhibit.

The monitor accepts +4 to +20 mA current inputs or any

proportional voltage inputs between -10 Vdc and +10 Vdc, in

addition to monitoring “dry” or “wet” contacts which can be a

sensor, switch, or relay.

Bently Nevada ORBIT 60 SERIES TC/RTD Temperature Module

Description

TC/RTD Temperature Module

The primary purpose of temperature modules is to interface

to the temperature transducers and convert the signal into a

digital representation. These modules condition and digitize

the inputs  at a rate that completely encompasses the signal

content and allows for removal of typical noise sources.

The Orbit 60 Series TC/RTD Temperature Input Modules

provide six channels of either Thermocouple (TC) or Resistive

Temperature Detector (RTD) temperature input sensors.

Each channel of the Orbit 60 Series TC/RTD input module is

individually configurable for sensor type and range using

Orbit Studio configuration software.

The RTD/TC inputs reference the internal system ground, and

for this reason, should only connect to transducers isolated at

the sensing end.

These modules occupy a single slot. The module OK LEDs

indicate proper functioning and the LINK LEDs indicate good

system communication. Six Channel Status LEDs on the utility

side of the module indicate a connected sensor in OK condition.

Sensor Types

TC sensors – The thermocouple configured channels provide

cold junction compensation for any J, K, E, or T Type

Thermocouple.

RTD sensors – The RTD configured channels can be

connected to the following:

• 3-Wire 100 Ohm Platinum 0.00392 RTD

• 3-Wire 100 Ohm Platinum 0.00385 RTD

• 3-Wire 10 Ohm Copper RTD

• 3-Wire 120 Ohm Nickel RTD