Johnson Controls 4007ES IDNet 2 addressable device control

IDNet 2 addressable device control

The 4007ES Hybrid provides an IDNet 2 addressable initiating device

signaling line circuit (SLC) that supervises wiring connections and

the individual device communications status on the SLC. With 2

wire IDNet 2 SLCs, initiation, monitoring, and control devices such as

manual fire alarm stations, TrueAlarm sensors, control relays, and

sprinkler waterflow switches can communicate their identity and

status and receive fire alarm system control. Additional addressable

interface modules include circuit isolators, conventional IDC zone

adapters, and interface to other system circuits such as fans,

dampers, and elevator controls.

IDNet 2 addressable device operation

Each addressable device on the IDNet 2 communication channel

is continuously interrogated for status condition such as: normal,

off-normal, alarm, supervisory, or trouble. Both Class B and

Class A operation is available. Sophisticated poll and response

communication techniques ensure supervision integrity and enables

T-tapping of the circuits for Class B operation. Devices with LEDs

pulse the LED to indicate receipt of a communications poll and can

be turned on steady from the panel. With addressable devices,

the location and status of the connected device is monitored,

logged, and displayed on the operator interface LCD. For precise

identification, each device has its own 40-character custom label.

Johnson Controls 4007ES Hybrid, Fire Detection and Control Unit

Mechanical description

• Locking door with polycarbonate window.

• Latching front panel assembly swings forward for convenient

internal access.

• Smooth box surfaces are provided for locally cutting conduit

entrance holes exactly where required.

• Modules are power-limited except as noted, such as relay

modules.

• The battery compartment at the bottom, has space for two

batteries, up to 18 Ah. You can mount batteries within the cabinet

without interfering with module space. Charger capacity is up to

33 Ah. For information about batteries greater than 18 Ah and

external battery cabinets, see Module and accessories selection

information.

• Cabinet assembly design has been seismic tested and is certified

to IBC and CBC standards also to ASCE 7 categories A through

F, requires battery brackets. For more information, refer to data

sheet S2081-0019.

• Seismically compliant under the State of California Statewide

Office of Housing and Development (OSHPD) Special Seismic

Certification (SSC) program guidelines. Refer to Simplex Seismic

Application Guide 579-1213 and Battery Brackets for Seismic Activity

Applications S2081-0019 for details.

Johnson Controls 4007ES Series Convenient status information

Operator interface

Convenient status information

If the locking door is closed, through the glass window, you can view

the display status of the LEDs. The user interface is a 4.3 in. (109

mm) diagonal color touchscreen LCD with separate status LEDs. See

Figure 2.

LED indicators describe the general category of activity displayed and

the LCD provides more detail. Authorized users can unlock the door

to gain access to the control functions and scroll through the display

for additional detail.

Operator interface and software features

• Convenient and detailed operator information is easily accessible

using a logical, menu-driven touchscreen display with password

access control

• Multiple automatic and manual diagnostics for maintenance

reduction

• Alarm and Trouble History Logs, up to 1000 entries for each, 2000

total events. You can view these events from the display or print

them out on connected printer, or download them to a service

computer.

• Module level ground fault searching assists installation and

service by locating and isolating modules with grounded wiring

• WALKTEST silent or audible system test performs an automatic

self-resetting test cycle and supports up to eight WALKTEST

groups

• Install Mode can group multiple troubles for uninstalled modules

and devices into a single trouble condition, typical with future

phased expansion. With future equipment and devices grouped

into a single trouble, operators can clearly identify events from

the commissioned and occupied areas.

Johnson Controls 4007ES Series Fire Detection and Control Units

Introduction

4007ES Series Fire Detection and Control Units provide extensive

installation, operator, and service features with point and module

capacities suitable for a wide range of system applications. You can

configure Panels for stand alone or networked fire control operation.

The convenient and intuitive color touchscreen provides easy access

for typical system response actions and for detailed system review or

configuration updates with password control to limit user access.

Standard conventional IDCs and addressable IDNet 2

communications provide flexibility for both new and retrofit systems.

For IDC and NAC, you can select EOL resistor values to match a wide

range of existing initiating device circuits and notification appliance

circuits.

ES panel compatibility with ES Net

Simplex ES Network (ES Net) is a next generation IP-based fire

network that uses industry standard network technology and

infrastructure, and facilitates simplified network upgrades, easy

terminal connectivity and IP file transfer between nodes, and

advanced network diagnostics.

You can upgrade ES fire alarm control units (FACUs) to operate on an

ES network by adding an ES Net NIC to the panel.

To upgrade an existing 4120 network to ES Net, you must replace all

of the 4120 NIC cards on the network loop with ES Net NICs.

Note: ES Net NICs and 4120 NICs cannot be mixed on the same

network loop.

For more detailed information about ES Net, refer to data sheet

S4100-0076. and talk to your local Simplex product supplier.

Johnson Controls 4007ES Optional modules and connections include

Software feature summary:

• Current and previous panel configuration is maintained in on

board memory

• An internal Ethernet service port is available for service computer

connections to perform configuration updates, downloads and

uploads, report downloads, and update system software

• You can use the internal USB interface with a memory stick to

store job revisions, update revised jobs and panel software, and

save detailed system reports from the panel.

Optional modules and connections include:

• Fire alarm network interface card (NIC) for ES Net or 4120 network

• Peer-to-peer network communications, supports either Class B or

Class X operation

• Point or Event DACT assembly for Connected Services Gateway

• Up to two additional IDNet 2 addressable device output loop

connections with short circuit fault protection and with 75

additional point capacity each.

• Front mounted 32 LED and 32 LED/switch annunciator with

custom label inserts. LEDs are programmable for up to 32

IDC zones of alarm and trouble annunciation or other custom

annunciation requirements.

• Remote LED annunciator support through remote user interface

(RUI) communications port for use with UTP wiring.

• Dual RS-232 ports for printer, PC annunciator, or third party interface.

• Alarm relays and auxiliary relays.

• City connections, with or without a disconnect switch.

• 4009 IDNet NAC Extenders to extend NAC capability for power and

distance

• Battery brackets for seismic area protection. 

Johnson Controls 4007ES Electrically isolated IDNet 2 addressable initiating device SLC

Electrically isolated IDNet 2 addressable initiating device SLC:

• Provides built-in short circuit isolation for monitoring and

control of TrueAlarm analog sensors and IDNet communications

monitoring and control devices. For use with either shielded or

unshielded, twisted or untwisted single pair wiring. Outputs are

Class A or Class B.

• Standard panel signaling line circuit (SLC) provides up to 100

addressable points. Optional additional loop expansion modules

provide an additional isolated loop with short circuit isolation for

the IDNet 2 channel. Each loop expansion module also provides

an additional 75 addressable points.

Power supply:

• Four notification appliance circuits (NACs), you can select as Class

A or Class B with 6 A total available current

• You can select the NAC EOL resistor value from a wide range of

resistance values for retrofit convenience

• For additional notification power capacity, use a 4009 IDNet NAC

Extender.

• Battery backup charging of up to 33 Ah. Up to 18 Ah for cabinet

mounted batteries and up to 33 Ah for batteries mounted close

nippled, in a remote battery cabinet.

General mechanical:

• Red or platinum cabinet. Rated NEMA 1 and IP30.

4007ES Listings reference:

• UL 864 – Control Units, System (UOJZ). Control Unit Accessories,

System, Fire Alarm (UOXX). Control Units, Releasing Device Service

(SYZV)

• UL 2017 – Emergency Alarm System Control Units (CO detection),

(FSZI)

• ULC-S559 – Central Station Fire Alarm System Units (DAYRC)

• ULC-S527 – Control Units, System, Fire Alarm (UOJZC). Control Unit

Accessories, System, Fire Alarm (UOXXC). Control Units, Releasing

Device Service (SYZVC)

Johnson Controls 4007ES Fire Control Units

Features

Compatible with Simplex ES Net and 4120 fire alarm networks

Satisfies a variety of new and retrofit applications

4.3 in. (109 mm) diagonal color touchscreen display:

• Provides detailed system status and point information.

• Supports dual language selection, including unicode character

languages.

• A custom background display appears when operation is normal.

Eight point zone/relay module:

• For each point, you can select as an IDC input or Relay output.

Class A IDCs require two points, one out and one return. One

module is standard and you can field install up to three additional

modules for a total of four 8 point zone/relay modules for each

system.

• You can configure each point on the IDC/Relay module as a

control relay rated 2 A at 30 VDC resistive as either normally open

or normally closed.

• Power comes directly from the power supply or through the

optional 25 VDC Regulator Module

• You can select the IDC end-of-line (EOL) resistor value from a wide

range of resistance values for retrofit convenience

Johnson Controls System Accessories, LCD Annunciators

Operation

System Controls. Notification appliances can be

deactivated by pressing the “ALARM SILENCE” switch.

(Exact operation is determined by the host control panel

such as visible appliances remaining on until system is

reset.) Pressing the “SYSTEM RESET” switch restores

the system to normal operation. When system activity is

normal, the LCD displays the time, date, and “SYSTEM

IS NORMAL.”

Control Switches. Four programmable “CONTROL”

switches and associated LEDs are included. Typical

applications include manual evacuation, door holder

release bypass, and elevator capture bypass.

Keyswitch Enable. All switches on the annunciator are

controlled by the “ENABLE” keyswitch with a key that is

removable only in the disabled position. A brief

lamp/LCD test is performed whenever the keyswitch is

changed from enabled to disabled.

Battery Backup Operation. During battery backup,

the LED backlighting is disabled to conserve battery

power. When an annunciator switch is activated, the

backlighting is automatically enabled. After

approximately 30 seconds of inactivity, the backlighting

will again be disabled.

*  This product has been approved by the California State

Fire Marshal (CSFM) pursuant to Section 13144.1 of the

California Health and Safety Code. See CSFM Listing

7120-0026:0179 for allowable values and/or conditions

concerning material presented in this document. It is

subject to re-examination, revision, and possible cancellation.

Accepted for use – City of New York Department of Buildings

– MEA35-93E. Additional listings may be applicable; contact

your local Simplex product supplier for the latest status.

Listings and approvals under Simplex Time Recorder Co.

are the property of Tyco Fire Protection Products.

Johnson Controls Remote Control and Annunciation is provided using an 80 character

Description

Remote Control and Annunciation is provided using

an 80 character, back-lit, alphanumeric display.

Information is presented in clear, descriptive English

language and includes: Point Status (alarm, trouble, etc.);

Alarm Type (smoke detector, manual station, etc.);

Number of System Alarms, Supervisory Conditions,

and Trouble Conditions; and a Custom Location Label.

Wiring. A single twisted wire pair provides serial RUI

communications that also supports other Simplex serial

annunciators on the same wire pair.

Multiple Indications. Alarm, Supervisory, and Trouble

conditions are also indicated by dedicated LEDs and a

tone-alert audible sounder. Each condition has a dedicated

acknowledge push-button switch that silences the

tone-alert but leaves the LED on until all conditions in

that category are restored to normal. Switch operation is

either globally or individually acknowledgeable,

determined by the control panel operation.

Repeated operation of the appropriate acknowledge

switch will scroll the LCD display showing activity in the

sequence of occurrence. The tone-alert also pulses to

indicate the operation of any of the push-button switches.

Consult local code requirements for guidance in

determining applications and location of the 4603-9101

LCD annunciator.

Johnson Controls 4603-9101 LCD Annunciator for 4100ES and 4100U Fire Alarm Control Panels

Features

Remote LCD annunciator for use with Simplex® model:

 4100ES and 4100U fire alarm control panels

 Legacy products 4100. 4120. and 4020 fire alarm control

panels, and 4100/4120 Universal Transponders

Information display features:

 Maintained display of first alarm is available with

4100ES and with 4100U at software revision 11.11 or higher

 Wide viewing angle, super-twist LCD technology with

green LED backlighting

 Two lines of 40 characters each

 LED status indicators

 During battery backup, backlighting is disabled until

there is switch activity

Controls include:

 Switches for system acknowledge, alarm silence, and

system reset

 Four programmable control switches

 Lamp/LCD test

Wiring information:

 RUI (Remote Unit Interface) communications require a

single twisted wire pair (see p. 3 for more information)

 Separate wiring is required for 24 VDC control panel power

Flush mount on standard electrical boxes Options:

 2975-9206. Surface mount box

 4603-9111. Brushed stainless steel trim

UL Listed to Standard 864