KEBA KeConnect DM 27x/A Digital hybrid modules
Digital inputs
DM 272/A DM 276/A
Number / wiring of inputs 8x sink 6x source
Input type Type 1 (acc. to EN 61131-2)
Voltage range for “1” 15 V ≤ UH ≤ 30 V
Voltage range for “0”-3 V ≤ UL ≤ 5 V
Debouncing Configurable 1 ms, 100 ms
Cycle time 1 ms
Status display Green LED
Galvanic isolation Yes, electric strength 707 V with isolated ground connection
Interrupt inputs
Number of inputs Two of the digital inputs can be used as interrupt inputs
Voltage range for “1” 15 V ≤ UH ≤ 30 V
Voltage range for “0”-3 V ≤ UL ≤ 5 V
Response time of the K-bus interrupt 50 μs
Status display Green LED
Galvanic isolation Yes
Digital outputs
DM 272/A DM 276/A
Number / wiring of outputs 8x source 8x sink
Nominal voltage 24 V DC
Processing time 1 ms
Nominal current of digital outputs 2 A at 50 % simultaneity
Protection facility Short-circuit protection
Max. inductive load 1 J at max 0.2 Hz
Status display Orange LED
Galvanic isolation Yes, from the control electronics and between one another,
electric strength 707 V with isolated ground connection
Dimensions, weight
Height 120 mm
Width 22.5 mm front plate / 32.5 mm incl. K-bus plug
Depth 100 mm
Weight 135 g
Environmental conditions
Operating temperature +5 °C … +55 °C
Storage temperature-40 °C … +70 °C
Relative air humidity 10 % to 95 % (non-condensing)
Vibration resistance / shock resistance Acc. to EN 61131-2
General
Supply voltage 24 V DC from front
(nominal voltage tolerance: 19.2 V to 30 V, acc. to EN 61131-2)
24 V DC from K-bus, 5 V DC from K-bus
Overvoltage category II
Protection class III acc. to EN 61131-2
Addressing on K-bus Via 16-digit address switch, on the side
Type of terminals Open – pitch 5.08 mm
Max. power consumption K-bus 24 V 1.9 W
Max. power consumption K-bus 5 V 0.4 W