KEBA KeConnect DM 27x/A Digital hybrid modules


Digital inputs

DM 272/A DM 276/A

Number / wiring of inputs 8x sink 6x source

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Debouncing Configurable 1 ms, 100 ms

Cycle time 1 ms

Status display Green LED

Galvanic isolation Yes, electric strength 707 V with isolated ground connection

Interrupt inputs

Number of inputs Two of the digital inputs can be used as interrupt inputs

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Response time of the K-bus interrupt 50 μs

Status display Green LED

Galvanic isolation Yes

Digital outputs

DM 272/A DM 276/A

Number / wiring of outputs 8x source 8x sink

Nominal voltage 24 V DC

Processing time 1 ms

Nominal current of digital outputs 2 A at 50 % simultaneity

Protection facility Short-circuit protection

Max. inductive load 1 J at max 0.2 Hz

Status display Orange LED

Galvanic isolation Yes, from the control electronics and between one another,

electric strength 707 V with isolated ground connection

Dimensions, weight

Height 120 mm

Width 22.5 mm front plate / 32.5 mm incl. K-bus plug

Depth 100 mm

Weight 135 g

Environmental conditions

Operating temperature +5 °C … +55 °C

Storage temperature-40 °C … +70 °C

Relative air humidity 10 % to 95 % (non-condensing)

Vibration resistance / shock resistance Acc. to EN 61131-2

General

Supply voltage 24 V DC from front

(nominal voltage tolerance: 19.2 V to 30 V, acc. to EN 61131-2)

24 V DC from K-bus, 5 V DC from K-bus

Overvoltage category II

Protection class III acc. to EN 61131-2

Addressing on K-bus Via 16-digit address switch, on the side

Type of terminals Open – pitch 5.08 mm

Max. power consumption K-bus 24 V 1.9 W

Max. power consumption K-bus 5 V 0.4 W

KEBA KeConnect DM 27x/A Product features

Product features

• Up to 8 digital inputs

• 8 digital 2 A outputs

• 2 digital inputs with interrupt

• Short-circuit detection

• Permanently short-circuit proof

• Electronic rating plate

Short description

The DM 27x/A series is a digital input/output module of the KeConnect C2 product line and enables the

connection of 6 or 8 digital inputs and 8 digital outputs. 24 V DC control signals are captured by the

digital inputs and transmitted galvanically isolated to the higher-level automation device. In addition, two

of the digital inputs can be used as interrupt inputs.

The digital outputs switch the 24 V DC control signals of a CPU module galvanically isolated from the

connected actuators. In addition to the short-circuit connection, outputs that cause short circuits can be

switched off individually.

This module is attached directly to a CPU module or can be operated with all KEBA controls by means of a

bus coupler.

Digital inputs

DM 272/A DM 276/A

Number / wiring of inputs 8x sink 6x source

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Debouncing Configurable 1 ms, 100 ms

Cycle time 1 ms

Status display Green LED

Galvanic isolation Yes, electric strength 707 V with isolated ground connection

KEBA KeConnect DO 242/B, DO 272/A Digital output modules

Digital outputs

DO 242/B DO 272/A

Number of outputs 8 14

Nominal voltage 24 V DC

Processing time 1 ms

Nominal current of digital outputs 2 A at 50 % simultaneity

Galvanic isolation Yes

Status display Orange LED

Protection facility Short-circuit protection

Max. inductive load 1 J at max 0.2 HzC

Dimensions, weight

Height 120 mm

Width 22.5 mm front plate / 32.5 mm incl. plug

Depth 100 mm

Weight 130 g

Environmental conditions

Operating temperature +5 °C … +55 °C

Storage temperature-40 °C … +70 °C

Relative air humidity 10 % to 95 % (non-condensing)

Vibration resistance / shock resistance Acc. to EN 61131-2

General

DO 242/B DO 272/A

Supply voltage 24 V DC from front (nominal voltage tolerance: 19.2 V … 30 V, acc. to EN 61131-2)

24 V DC from K-bus, 5 V DC from K-bus

Overvoltage category II

Protection class III acc. to EN 61131-2

Addressing on K-bus Via 16-digit address switch, on the side

Type of terminals Open – pitch 5.08 mm

Displays on the front plate 16 signal status LEDs

Max. power consumption K-bus 24 V 2.1 W 2.1 W

Max. power consumption K-bus 5 V 0.4 W 0.4 W

KEBA KeConnect DO 242/B, DO 272/A Product features

Product features

• 8 or 14 digital outputs

• Short-circuit detection and diagnosis

• Permanently short-circuit proof

• Current load capacity 2 A at 50 % simultaneity

• Fast shutdown function for inductive loads

• Electronic parameter chip

Short description

Digital output modules DO 242/B and DO 272/A enable the connection of up to 14 digital outputs. The

digital outputs switch the 24 V DC control signals of a central module galvanically isolated from the

connected actuators and are designed for a load of up to 2 A at 50 % simultaneity.

The modules are equipped with a fast shutdown function that enables a rapid shutdown of inductive

loads, e.g., hydraulic valves. Machine processes can thereby be accelerated and productivity increased.

The operational safety is ensured by the permanent short-circuit protection of the outputs. Should a short

circuit occur, it is detected and reported to the control module.

These modules are attached directly to a CPU module or can be operated with all KEBA controls by means

of bus couplers.

KEBA KeConnect DI 240/B, DI 260/A Digital input modules

Interrupt inputs

Number of inputs 2 (DI0. DI1) of the digital inputs

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Response time of the K-bus interrupt 100 μs with 5 kHz input filter

Status display Green LED

Galvanic isolation Yes

Dimensions, weight

Height 120 mm

Width 22.5 mm front plate / 32.5 mm incl. K-bus plug

Depth 100 mm

Weight 130 g

Environmental conditions

Operating temperature +5 °C … +55 °C

Storage temperature-40 °C … +70 °C

Relative air humidity 10 % to 95 % (non-condensing)

Vibration resistance / shock resistance Acc. to EN 61131-2

General

I/O supply voltage 24 V DC from K-bus

5 V DC from K-bus

Overvoltage category II

Protection class III acc. to EN 61131-2

Addressing on K-bus Via 16-digit address switch, on the side

Type of terminals Open – pitch 5.08 mm

Max. power consumption K-bus 24 V 1 W

Max. power consumption K-bus 5 V 0.4 W

KEBA KeConnect DI 240/B, DI 260/A Product features

Product features

• Up to 16 digital inputs

• 2 digital inputs with interrupt

• Electronic parameter chip

• Configurable input filter

Short description

The digital input module of the DI 2xx/x series enables the connection of 8 (DI 240/B) or 16 (DI 260/A)

digital inputs.

24 V DC control signals are captured by the digital inputs and transmitted galvanically isolated to the

higher-level auto mation device. In addition, two digital inputs can be used as interrupt inputs.

These modules are attached directly to a CPU module or can be operated with all KEBA controls by means

of bus couplers.

Digital inputs

DI 240/B DI 260/A

Number of inputs 8 16

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Status display Green LED

Galvanic isolation Yes, electric strength 707 V with isolated ground connection

Cycle time 1 ms

Debouncing Configurable 1 ms, 100 ms

Interrupt inputs

Number of inputs 2 (DI0. DI1) of the digital inputs

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Response time of the K-bus interrupt 100 μs with 5 kHz input filter

Status display Green LED

Galvanic isolation Yes

KEBA KeControl C5 – FE 560 Multi-protocol fieldbus expansion card

Product features

// 1 x EtherCAT / EtherNet/IP / PROFINET

// Plug connection for

KeControl C5 control modules

Brief description

The Ethernet-based fieldbus card FE 560 can be connected on

the left of the KeControl C5 controllers using the Card Edge connector.

This allows the exchange and processing of process data between

the higher-level control and the KeControl C5 control.

All relevant protocols such as EtherCAT, EtherNet/IP and PROFINET are supported.

KEBA KeControl C5 – FE 560 Technical specifications

Technical specifications

Interfaces

KeControl C5 control module 1 x Card Edge connector

EtherCAT slave / EtherNet/IP adapter /

PROFINET IO-Device 2 x RJ45

Dimensions

Height 106 mm

Width 26.5 mm (when installed)

Depth 82.5 mm (snap-on height 77.5 mm)

Weight 95 g

Environmental conditions

Operating temperature 0 °C to +55 °C

Storage temperature-40 °C to +70 °C

Relative humidity 10 % to 95 % (non-condensing)

Vibration/shock resistance According to EN 61131-2

General data

Overvoltage category II

Protection class III according to EN 61010-2-201

Certification

CE 2014/30/EU and 2011/65/EU

UL UL 61010-1 and UL 61010-2-201

UKCA Conformity with relevant statutory requirements

KEBA KeControl C5 FE 57x Technical specifications

Technical specifications

Dimensions

Height 106 mm

Width 26.5 mm (when installed)

Depth 82.5 mm (snap-on height 77.5 mm)

Weight 95 g

Environmental conditions

Operating temperature 0 °C to +55 °C

Storage temperature-40 °C to +70 °C

Relative humidity 10 % to 95 % (non-condensing)

Vibration/shock resistance According to EN 61131-2

General data

Overvoltage category II

Protection class III according to EN 61010-2-201

Interfaces

FE 571 FE 573

KeControl C5 control module 1 x Card Edge connector

EtherCAT master 2 x RJ45 2 x M8

Certification

CE 2014/30/EU and 2011/65/EU

UL UL 61010-1 and UL 61010-2-201

UKCA Conformity with relevant statutory requirements

KEBA The FE 57x fieldbus master cards

Product features

// 2 x EtherCAT master interfaces

// Plug connection for

KeControl C5 control modules

Brief description

The FE 57x fieldbus master cards can be connected on the left of the

KeControl C5 controllers using the Card Edge connector.

They make it possible to create additional EtherCAT master interfaces

on the controller and thus an expansive set-up of plants and machines

through the use of numerous fieldbus components.

The EtherCAT interfaces can be supplied either with M8 or

with RJ45 connectors. Depending on the requirements,

this provides suitability for individual industrial applications.

The built-in switch supports a star topology of the EtherCAT

slaves without the need for additional hardware.

Search for products