Segment Check
When first connected, the FBT-6 gathers data for all of its monitoring
functions. If all the measured data is within an acceptable range, the
Monitor displays “ALL MEASUREMENTS OK”.
Voltage
The DC voltage on the network is shown. Measurements over 9 volts
are OK. The maximum input voltage is 32.0 volts.
Device Count
If there are fieldbus devices active on the network, the Monitor counts
them. If the count has remained the same since the initial network
check was performed, the display shows “OK”.
Note: on Foundation™ fieldbus networks, the Link Active Scheduler
(LAS) is considered a device and, as such, is included in the count.
The FBT-6 is more sensitive to missed communications than most PC
monitoring software. As a result, a device may still show up on PC
monitoring software, even though the FBT-6 has removed the device
from its internal list of active devices. Devices having communication
difficulties may show up on the FBT-6 as repeatedly being added or
dropped. If a device leaves the network, the display shows “–”; if a
new device is added it shows “+”.